DCS for Steam Turbine of a Thermal Power Plant
Abstract
In order To increase the performance and the flexibility of the recentthermal power plant control, a DCS can be used.
The aim of this Project is to study the Distributed Control System (DCS)
and its application on a thermal Power Plant. A thermal power plant and its
operation are described, and the DCS is implementedon the main element of the
thermal power plant—the Turbine.
Key words: Thermal power Plant, Steam Turbine, synchronous Generator, DCS,
HMI/GUI, LAN, Ethernet, I/O Bus, Network Protocols,RTU, PLC, PID Controller
I- Introduction:
Most modern thermal power plants generate from 125 MW to 1000 MW of power.Any thermal power plant consists of a fuel handlingsystem, boiler, turbine, generator,
transformer, water handling, emission control system and other complementary accessories.
All these units are managed in such a way to generate, regulate electricity and ensure a good
product to the consumer.
A thermal power plant produces electricity startingfrom an energy source. This source
can be natural gas, oils, nuclear or even solar energy. This energy source transforms the fluid,
usually water, to a vapor. This vapor enters a turbine at high pressure and turns its shaft,
which, by the way, turns the shaft of an alternator. The turbine transforms thermal energy into
a mechanical one, and the generator transform this mechanical energy into electrical energy.
To make the turbine turn, the pressure of the vaporat the output has to be lower than
that of the input. This is done by condensing the vapor downstream in the turbine using a cold
source like water. The condensed water is always used as the source of the vapor; which
makes a closed thermodynamic cycle.
There are different types of thermal plants: flammable, nuclear, solar and geothermal.
In this chapter, we are going to have a look at oneof the thermal plants that is CAP-DJINET
thermal power plant.
II- CAP-DJINET Power Plant:
CAP-DJINET power plant belongs to SONALGAZ Company.It is located at CAB-DJINET, in the front of the sea, in BOUMERDES. It has been constructed with theassociation of the Austro-German companies: SIEMENS-KWU-SGP who were in charge of
the study and the supervision of the plant’s construction. Another company was Spanish
(DRAGARDOS) which has been in charge for the installation of the water pumping and
pipelines unit that pumps water from the sea. In addition, the Algerian companies: ENCC,
ETTERKIB, BATIMETAL, GENISIDER, INERGA, SNLB, PROSIDER, ENATUB, SNIC,
GTP, SONATRAM, and SOGEP were associated in the construction of CAP-DJINET.
CAP-DJINET power plant contains 4 thermal-vapor units with a capacity of about 176
MW each, and a total of 706 MW. 672MW are sent to the network and 32MW are used
internally in the plant. A boiler that serves the plant consumes 40,000 Nm3 gas per hour when
operating at full load. This gas is pipelined from HASSI R’MEL to CAP-DJINET.
III- Unit description:
Fuel (gas) is fed into the boiler where it is burned in order to heat water and rise itstemperature to 540°C (1000F) to produce steam that has a pressure of about 160 bar at the
boiler exits. As it enters the turbine, the steam is at a pressure between 138 to 140 bar. The
steam expands through the turbine, which consists of rows of blades attached to a shaft. The
steam turns the blades of the turbine, which then turn the shaft of a generator, made up of
magnets rotating between coils. The rotation of thegenerator induces alternating current in
the coils of the stator; this is the produced electricity. To ensure that the alternating current is
maintained constant at the standard frequency (50 Hertz), both turbine and generator rotate at
a constant speed (3000 rpm). The produced output voltage (15.5 kV) will be converted to 6
KV by step-down transformer for internal use, and to 220 kV by a step-up transformer, in
order to ensure efficient transmission over the entire network.
A simple schematic of CAP-DJINET thermal Power Plant is shown in Figure I-01
The production of electricity at the power plant ofCAP-DJINET starts from the
thermal energy and takes different transformations;these transformations occur at different
units that are mainly:
• The Boiler
• The steam turbine
• The synchronous generator
• The transformer
• The condenser
III-1- The steam generator (Boiler):
The boiler (usually called a steam generator) is a closed vessel in which water flows in
transporting tubes. This water is heated under highpressure and transformed into steam that
turns the group-turbine-generator. The type of boiler is the drum one, which means a large
drum; it is used as a reservoir for fluid (no extracting pumps are used to feed back the water
into furnace chamber). At the boiler, the steam reaches a temperature of 540° and a pressure
of 160 bars.
III-2- Steam turbine:
The steam turbine is a mechanical device that converts thermal energy frompressurized steam into useful mechanical energy to rotate the shaft.
The turbine makes use of the fact that steam attains a high velocity, when passing
through a small opening. The attained velocity during expansion depends on the initial and
final heat content of the steam. This difference inheat content represents the heat energy
converted into kinetic energy during the process. The steam turbine is composed of: high
pressure (HP), medium pressure (MP), and low pressure (LP) cores. All these units turn at a
speed of 3000 TR/MIN.
III-3- The Synchronous generator:
Synchronous generators (alternators) which convert mechanical energy to electricalone with an alternating current (AC), consist of two essential elements: the stator and the
rotor. A direct current (DC) is applied to the rotor winding to produce a magnetic field. By the
rotation of the rotor, a three-phase voltage is induced in the stator windings by the rotation of
the magnetic field. The parameters of the generatedvoltage are: apparent power of 220 MVA,
power of 176 MW, voltage of 15500 V±10%, current of8165 A, and a frequency of 50 Hz.
The generator of CAP-DJINET is divided into three alternators shown below:
The function principle of the generator is described as follows:
The turbine turns the exciting pilot which containsa natural magnet’s rotor. This
alternator generates a current at the stator which is converted to DC current by the Thyristor
bridge. The voltage regulator controls the RMS of the DC current by changing the firing
angle. After that, the DC current is transferred tothe stator of the principle exciter. The
principle exciter generates an AC current that is converted to a DC current by a turning diode
bridge. The DC current is transferred to the rotor of the main alternator; this current is called
the exciting current. The main alternator generates a 3 phase current with a voltage that
depends on the exciting current.
III-4- The Condenser:
The condenser is a heat-exchange system, mounted atthe outlet of the low pressure
core of the steam turbine to condense steam. The condenser increases the efficiency of the
turbines. From the bottom of the condenser, powerful pumps recycle the condensed steam
(water) back to the feed water heaters for reuse. The heat absorbed by the circulation cooling
water in the condenser tubes must also be removed to maintain the ability of the water to cool
as it circulates. A proper operation of the condenser requires access to a large amount of
water; therefore, the sea water is used.
It has been proved that the efficiency can be improved, when feeding back heated
water; the gas consumption is much lower than that for a cold distilled water.
III-5- The heaters:
Heaters are the main elements of the Rankin cycle. Their role is to gradually heat up
both the water coming from the condenser and the one extracted from high and intermediate
pressure parts of the turbine.
III-6- The transformer:
There are two main transformers, the step down transformer that converts the 15.5 KV
to 6 KV for internal uses, and the step up transformer that converts the voltage from 15500 V
to 220 kV; this will decrease the current, reduce energy loss and ensure efficient transmission
over the network.
IV- Steam Plant (Rankin) cycle:
The Rankin cycle is the most widely used cycle for electric power generation. The
steam cycle is based on dry saturated steam being supplied by a boiler to the turbine. The
steam from the turbine exhausts to a condenser, from which the condensed steam is pumped
back into the boiler passing through heaters. Higher plant efficiency is obtained if the steam is
initially superheated, and this means that less steam and less fuel are required for a specific
output. Heaters are often used in large utility plants because they give additional steam energy
to the low-pressure portion of the turbine; thus, increasing the overall plant efficiency.
By adding regenerative feed water heating, the Rankin cycle is improved significantly.
high pressure core, two from medium pressure core, and one from the condenser) to heat the
fed-back water as it is pumped from the condenser to the boiler to complete the cycle.
V- Overall plant presentation:
The next page illustrates the overall thermal powerplant construction, and shows the
main components with the auxiliary equipments.
II- distributed control system:
I- Introduction:
Early minicomputers were used in the control of industrial processes since the
beginning of the 1960s. The IBM 1800, for example, was an early computer that had
input/output hardware to gather process signals in a plant for conversion from field contact
levels (for digital and analog signals) to the digital domain.
The DCS was introduced in 1975. Honeywell produced a DCS called TDC 2000. At
roughly the same time, a Japanese electrical engineering firm Yokogawa produced its own
independently DCS called CENTUM systems. US-based Bristol also introduced their UCS
3000 universal controller in 1975. In 1980, Bailey (now part of ABB) introduced the
NETWORK 90 system. Similarly in 1980, Fischer & Porter Company (now also part of ABB)
introduced DCI-4000 (Distributed Control Instrumentation).
The DCS largely came out due to the increased availability of microcomputers and the
sudden increase of microprocessors’ use in the world of process control. Computers had
already been applied to process automation for sometime in the form of both Direct Digital
Control (DDC) and Set Point Control. The more conservative approach was Set Point
Control, where process computers supervised clusters of analog process controllers.
Workstations provided visibility into the process using text and character graphics.
Availability of a fully functional graphical user interface was a way away.
Central to the DCS model was the inclusion of control function blocks. Function
blocks evolved from early, more primitive DDC concepts of "Table Driven" software; one of
the first embodiments of object-oriented software. Function blocks remain as the predominant
method of control for DCS suppliers, and supported by key technologies.
Digital communication between distributed controllers, workstations and other
computing elements (peer to peer access) was one ofthe primary advantages of the DCS.
Attention was duly focused on the networks, which provided all the important lines of
communication that, for process applications, had to incorporate specific functions such as
determinism and redundancy.
II- Definition of the DCS:
Distributed Control Systems (DCS) use decentralized elements or processors, and use
communication systems to control distributed processes or complete manufacturing systems.
They do not require user intervention for routine operation, but may permit operator
interaction via a Supervisory Control and Data Acquisition (SCADA) interface, or Human
Machine Interface (HMI). Distributed Control Systems (DCS) consist of a remote control
panel, communications medium, and a central controlpanel. They use process-control
software and input/output (I/O) database. Some suppliers refer to their controllers as remote
transmission units (RTU) or Digital Communication Units (DCU). Regardless of their name,
distributed controllers contain terminal blocks, I/O modules, a processor, internal memories
and a communication interface; the input/output devices (I/O) can be integral with the
controller or located remotely via a field network.Today’s controllers have extensive
computational capabilities and, in addition to proportional, integral, and derivative (PID)
control, can generally perform logic and sequentialcontrol. The communications system is a
wired or wireless link with transmission over twisted pair, coaxial, or fiber optic cable that
connect the distributed controllers and the centralcontrol panel. The central control panel is a
SCADA or Human Machine Interface (HMI) based system; it employs one or several
workstations that can be configured. A server and/or applications processor may be included
in the system for extra computational, data collection, and reporting capability.
Figure II-01 represents the different levels of theDCS. The supervisory level contains
the control panel which is a Human Machine Interface (HMI) based system. The control level
contains the RTUs (PLCs). The device level or the process level contains the controlled
elements that control the process. The control network represents the communication system.
In a Distributed control system, the operator sendssetting values to the distributed
controllers and acquires data from them through thecommunication network; these data and
setting values are stored in the memory of the controllers. The controllers receive information
through input modules and send information through output modules. The input modules
receive information from input instruments in the process (e.g. switches, sensors,
transducers). The controller’s processors execute the instructions of the process. The output
modules update instructions of output instruments in the field (e.g. electro vanes, pumps). The
controllers typically use communication network to communicate with the actuators, sensors
and human machine interface eliminating the need for point-to-point wiring to each device.
III- Applications of DCS:
Distributed Control Systems are dedicated systems used to control manufacturing
processes that are continuous or batch-oriented, such as oil refining, petrochemicals, central
station power generation, pharmaceuticals, food & beverage manufacturing, cement
production and papermaking. DCSs are connected to sensors and actuators and use set point
control to control the flow of material through theplant. The most common example is a set
point control loop consisting of a pressure sensor,controller, and control valve. Pressure or
flow measurements are transmitted to the controller. When the measured variable reaches a
certain point, the controller instructs a valve or an actuation device to open or close until the
fluidic flow process reaches the desired set point.Large oil refineries have many thousands of
I/O points and employ very large DCSs. Processes can also include things like variable speed
drives, motor control centers and many others.
IV- Elements of DCS:
IV -1- FIELD DEVICES:
Field devices form the "eyes and ears" of a DCS. Devices such as reservoir level
meters, water flow meters, valve position transmitters, temperature transmitters, power
consumption meters, and pressure meters all provideinformation that can tell an experienced
operator how well a system is performing. All thesedevices transmit the information in a
form of an electric signal that can be analog or digital.
In addition, equipments such as electric valve actuators, motor control switchboards,
and electronic chemical dosing facilities can be used to form the "hands" of the DCS and
assist in automating the process of a system. The distributed controllers control the process by
sending an electric signal to the actuators that will convert the signal into the appropriate form
(pressure, position, speed or other form). Typical field instrumentations are:
– Switches and Pushbuttons – Flow Meters
– Level Transducers – Temperature Transmitters
– Pressure Switches – Gas Detector
– Control Relays – Actuators and Drives
IV -2- DISTRIBUTED CONTROLLERS:
IV -2-1- REMOTE TERMINAL UNITS (RTUS):
An RTU is a standalone data acquisition and controlunit, generally microprocessor
based, which monitors and controls equipment at some remote location from the central
panel. Its primary task is to control and acquire data from process equipment at the remote
location and to transfer this data back to a central control panel. It generally also has the
facility for having its configuration and controls dynamically downloaded programs from
central panel. There is also a facility to be configured locally by some RTU programming
unit. Although traditionally the RTU communicates back to some central panels, it is also
possible to communicate on a peer-to-peer basis with other RTUs.
There are two basic types of RTU - the "single board RTU" which is compact, and
contains fixed number of I/O on a single board, andthe "modular RTU" which has a separate
CPU module, and can have other linked modules like analog modules and other specialized
modules, normally by plugging into a common "backplane" (see figure II-02).
Typical RTU hardware modules include:
• Control processor and associated memory
• Analog inputs & analogue outputs
• Digital inputs
• Digital outputs
• Communication interface(s)
• Power supply
IV -2-2- PROGRAMMABLE LOGIC CONTROLLERS (PLCs):
A PLC (programmable logic controller) is a small industrial computer which
originally replaces relay logic with a combination of ladder–logic software and solid state
electronic input and output module. It has inputs and outputs similar to those an RTU has. It
contains a program which executes a loop, scanning the inputs and taking actions based on
these inputs. Originally the PLC had no communications capability, but they began to be used
in situations where communication was a desirable feature. Hence communication modules
were developed for PLC's, supporting Ethernet (for use in distributed control systems) and
MODBUS communications protocol for use over dedicated (wire) links(see Figure II-03).
They are often used in the implementation of a DCS’RTU as they offer a standard hardware
solution, which is very economically priced.
IV -3- CENTRAL CONTROL PANEL:
The central control panel contains computers with larger monitors running system
software. These computers are known as application work stations (AW), and work station
processors (WP). The control station contains localPrinters and shared printers connected to
the network to print reports, files and alarms failures records.
1- Workstation Processors (WP):
They are Operator terminals that do the following functionalities:
• Provide Human-machine Interface (HMI) for operatorsand provide a real time
interface between the operators and the DCS.
• Accept, process and store data from RTU/RPU
• Process regulation using the HMI
• Accept, process and store data from RTU
• Distribute data to controllers
2- Application Processors (AP):
The common functions of the APs are:
• Files server
• back up files and DCS controller programs Storage
• Files and data base storage
• System supervision and warning when failures occur in the system
• Execution of application software and programs (e.g. save history files,
making reports and statistics)
3- Application Workstation (AW):
This station can be used for AP and WP applications.
AP and WP can also replace the system server for files and data base storage.
IV-4- COMMUNICATION INTERFACES STANDARDS:
Regardless of the type of peripheral used, communication interfaces must be used to
achieve correct communication. Typical peripherals communicate in serial form at speeds
ranging from 110 to 19,200 bit/sec (baud), with parity and non parity, and use various
communication interface standards. An interface standard defines the electrical and
mechanical details that allow communication equipments from different manufacturers to be
connected together and to function efficiently.
IV-4-1- Serial Communication:
It occurs in serial form through simple, twisted-pair cables. Serial data transmission is
used for most peripheral communication devices. Serial communication allows peripheral
equipment, such as terminals, operator interface panels, and printers, to receive ASCII
characters. The most popular standards for serial communication is the RS-232. Other PLC
standards are the RS-422 and RS-485, which improve performance and give greater flexibility
in data communication interfaces.
The data communication links used with peripheral equipment can be unidirectional or
bidirectional. Unidirectional serial signal line is used where data transmission occurs in only
one direction (input or output devices). Devices that serve as both input and output devices
require bidirectional links. There are two ways to achieve this bidirectional communication.
First, a single data line can be used as a shared communication line. The data can be sent in
either direction, but only in one direction at a time. This operation is known as half duplex. If
simultaneous bidirectional communication is required, two lines can connect the PLC to the
peripheral. One line would be assigned permanently as an input, while the other would be a
permanent output. This mode is known as full duplex. This is illustrated in figure II-04.
IV-4-2- EIA RS-232 Standard:
The EIA RS-232 is a proclaimed standard set by the Electronic Industries Association
![](https://blogger.googleusercontent.com/img/b/R29vZ2xl/AVvXsEgtnbS7sjkZJtv7fTltPU2XS_aMhxbDqloiUWSXgwD0HO5AsfFeKaHo2mr8MG_dY2YFeV95D6pQnEPeApxw8WtQ6tS47xF7itliMIZldIiC5JtGNt5OlX3ouHOaDKlQ0uGviElrvP52Mebx/s400/Fig+2.05.jpg)
employs serial binary data interchange(see figure II-05).
The RS-232 standard defines 25 electrical connections. Theelectrical connections are
four groups:
• Data lines
• Control lines
• Timing lines
• Special secondary functions
IV-4-3- EIA RS-422 Standard:
The RS-422 standard overcomes some of the RS-232 shortcomings. Like the RS-232,
the RS-422 standard still deals with the traditional serial/binary switch signals of two voltage
levels across the interface. The RS-232 is an unbalanced link communication method
(master/slave relationship). The RS-422, however, is a balanced link (master/master or
master/slave). The RS-422 specifies electrically balanced receivers and generators that
tolerate and produce less noise. These provide superior performance up to 10,000 Kbit/sec,
Distances of up to 1200 m, and can be used in a network communication of up 10 devices. .
The EIA selected a 37-pin and 9-pin connectors for the RS-422 standard, because it satisfies
interface channel requirements.
IV-4-4- EIA RS-485 Standard:
The RS-485 standard, like the RS-422, has dual transmitting and receiving lines
(differential signals). This type of interface is best suited for industrial applications, because it
provides better electrical isolation from the PLC or host than the RS-422 standard. It is also
capable of being used in a network for multi-point communication (e.g., multiple transmitters
and receivers operated on a common media, up to 32 devices can be connected). Distances of
up to 1200 meter and Data rates of up to 10 Mbit/sec can be attained with this standard.
IV-4-5- Interface Converters:
Communications standards are used extensively in applications with a PLC or with a
computer in a network where one or more interfaces are used. Sometimes a PLC with an RS-232C or RS-422 communication interface must communicate with an RS-485 device. In this
case, an RS-232C–to–RS-485 converter (or an RS-422–to–RS-485 converter) can provide this
communication. These converters provide electrical isolation, in addition to longer distance.
IV-5- Communication Network:
The communications network is intended to provide the means by which data can be
transferred between the central control panel and the field-based controllers. The
Communication Network refers to the equipment and protocols needed to transfer data to and
from different sites. The medium used can either becable, telephone or radio.
Historically, DCS networks have been dedicated networks; however, with the
increased deployment of office LANs and WANs as a solution for interoffice computer
networking, there exists the possibility to integrate DCS LANs into office computer networks.
The technology came out with another network which is the I/O bus network, this
network is used by the intelligent field devices ofthe DCS, and this network is getting
popular. The most common types of I/O bus network are: FIELDBUS and PROFIBUS.
IV-5-1- LOCAL AREA NETWORK (LAN):
As control systems become more complex, they require more effective
communication schemes between the system components. Some machine and process control
systems require programmable controllers to be interconnected, so that data can be transferred
rapidly and easily to accomplish the control task.
A local area network is a high-speed, medium-distance communication system. For
most LANs, the maximum distance between two nodes in the network is at least one mile, and
the transmission speed ranges from 1 to 20 megabit/second. Also, most local networks
support at least 100 stations, or nodes. A special type of local area network, the industrial
network, is one which meets the following criteria:
• Capable of supporting real-time control
• High data integrity (error detection)
• High noise immunity
• High reliability in harsh environments
• Suitable for large installations
IV-5-1-1- ADVANTAGES OF LANS:
Before local area networks came into use, PLCs communicated through their
programming ports via a central computer (RS-232, RS-422 and RS-485). The disadvantages
of this method were that it limited the data rate of the PLC’s programming port. Also the
network would fail if the central computer failed due to the system’s star topology.
The local area network offers distinct advantages because it greatly reduces the cost of
wiring for large installations. It also uses a dedicated communication link to efficiently
exchange large amounts of usable data among PLCs and other hosts; Moreover, PLCs in the
network can communicate independently with each others.
IV-5-1-2- THE USE OF LAN:
Centralized data acquisition and distributed control are the most common applications
of local area networks. The use of LAN can provide the following functions:
• Communication between programmable controllers
• upload and download capability of a host computerto or from any PLC
• Reading/writing of I/O values and registers to any PLC
• monitoring of PLC status and control of PLC operation
IV-5-1-3- NETWORK TOPOLOGIES:
The topology of a local area network is the geometry of the network. A network’s
topology greatly affects its throughput rate, implementation cost, and reliability. The basic
network topologies used today are star, common bus, and ring (see figure II-07);however, a
large network may consist of multiple topologies.
A- Star topology:
The first PLC networks consisted of a multiport host controller with each port
connected to the programming port of a PLC or another intelligent device. Most
commercial computer installations are star networks. The main advantage of this
topology is that it can be implemented with a simple point-to-point protocol. Star
topology, however, has some disadvantages:
• It does not lend itself to distributed processingdue to the central node.
• The wiring costs are high for large installations.
• Messages must pass through the central node, resulting in low throughput.
• Failure of the central node will crash the network.
B- Bus topology:
The bus topology has a main trunk-line to which individual PLC nodes are
connected in a multi-drop fashion without the use of a network controller.
Common bus topologies are very useful in distributed control applications,
since each station has equal independent control capability. Moreover, common bus
topology is scalable (add, remove devices easily). The main disadvantage of this
topology is the dependency on a common bus which can be overcome with the use of
redundant bus. And it’s commonly known as dual node-bus in DCS.
Another configuration of the bus topology is the master/slave bus topology,
consisting of several slave controllers and one master network controller. The master
sends data to the slaves; if the master needs data from a slave, it will poll (address) the
slave and wait for a response. No communication takes place without the master.
C- Ring topology:
In this topology the data flow in one direction, with each node passing data on to the
next node and so on. A failure of any node (not just the master) will crash the network,
unless the failed node is bypassed. Some LAN manufacturers have overcome the
problem of node failure in a ring topology by using a wire center. The wire center
automatically bypasses failed nodes in the ring.
IV-5-1-4- NETWORK ACCESS METHODS:
An access method is the manner in which a PLC accesses the network to transmit
information. As mentioned in the previous section, a bus topology requires that the nodes take
turns transmitting on the medium. This process requires that each node is able to shut down
its transmitter without interfering with the network’s operation. The most commonly used
methods are: polling, collision detection, and token passing.
A- Polling
The access method most often used in master/slave protocols is polling. In
polling, the master interrogates each station (slave) in sequence to see if it has data to
transmit. The master sends a message to a specific slave and waits a fixed amount of
time for the slave to respond. The slave should respond by sending either data or a
short message indicating that it has no data to send. If the slave does not respond
within the allotted time, the master assumes that the slave is dead and continues
polling the other slaves. Polling is often referredto as the master/slave access method,
and the physical topology used is typically a bus type network.
B- Collision Detection
Collision detection is generally referred to as CSMA/CD (carrier sense
multiple access/collision detection). In this access method, each node with a message
to send waits until there is no traffic on the network and then transmits. While the
node is transmitting, it checks for the presence ofanother transmitter. If the circuit
detects a collision (two nodes transmitting at a time), the node will disable its
transmitter and wait a random amount of time beforeretransmission.
CSMA/CD uses a bus topology and operates over a half-duplex connection.
The most common example of CSMA/CD is Ethernet (or the IEEE 802.3). Can bus
and IEEE802.11 wireless networking technologies uses a similar version called
CSMA/CA (carrier sense multiple access/collision avoidance). In CSMA/CA the
device examines the media for the presence of a data signal. If the media is free, the
device sends a notification across the media of itsintent to use it. The device then
sends the data.
C- Token Passing
Token passing means that all participants on the network have a list of all the
participants on the network including itself, usually in the form of an address or node
number in ascending order. At any time, one of the participants has the token for an
amount of time. During this time it may send data to or request data from any other
node. When it is finished, or its maximum time has elapsed, it will 'pass-on' the token
to the next node in the list of participants and listen, as though it were a slave until it
receives the token again. The token-passing access method is preferred in distributed
control applications that have many nodes or stringent response time requirements. It
can be used also in star or ring topology.
IV-5-2- I/O BUS NETWORKS:
Advances in large-scale electronic integration and surface-mount technology, coupled
with trends towards decentralized control and distributed intelligence to field devices, have
created the need for a more powerful type of network—the I/O bus network. This new
network lets controllers better communicate with I/O field devices, to take advantage of their
growing intelligence.I/O bus networks allow PLCs to communicate with I/O devices in a
manner similar to how local area networks let supervisory PLCs communicate with individual
PLCs. This configuration decentralizes control in the PLC system, yielding larger and faster
control systems. The topology, or physical architecture, of an I/O bus network follows the bus
or extended bus (tree) configuration, which lets field devices (e.g., limit, photoelectric, and
proximity switches) connect directly to either a PLC or to a local area network bus.
The basic function of an I/O bus network is to communicate information with, as well
as supply power to, the field devices that are connected to the bus without the use of I/O
modules; therefore, the PLC connects to and communicates with each field I/O device
according to the bus’s protocol.
IV-5-2-1- TYPES OF I/O BUS NETWORKS:
I/O bus networks can be separated according to the following diagram:
A- Device Bus Networks
Interface with low-level information devices (e.g.,push buttons, limit switches,
etc.), which transmit data relating to the state ofthe device (ON/OFF) and its
operational status. These networks generally process only a few bits to several bytes of
data at a time.
B- Process Bus Networks
A process bus network is a high-level, open, digital communication network
used to connect analog field devices to a control system. The size of the information
packets delivered to and from these analog field devices is large, due to the nature of
the information being collected at the process level. The most commonly used process
bus networks are FIELDBUS and PROFIBUS. These networks can transmit data at a
speed of 1 to 2 megabits/sec. Process bus networks will eventually replace the
commonly used analog networks, which are based on the 4–20 mA standard for analog
devices. A PLC or computer communicates with a process bus network through a host
controller interface module using either FIELDBUS or PROFIBUS protocol format.
• FIELDBUS Process Bus Network
The FIELDBUS process bus network from the FIELDBUS Foundation
(FF) is a digital, serial, multiport, two-way communication system that
connects field equipment, such as intelligent sensors and actuators, with
controllers, such as PLCs. This process bus networkoffers the desirable
features inherent in 4–20 mA analog systems, such as:
A standard physical wiring interface
Bus-powered devices on a single pair of wires
Intrinsic safety options
The FIELDBUS network technology offers the following additional
advantages:
reduced wiring due to multi-drop devices
Compatibility among FIELDBUS equipment
Digital communication reliability
• PROFIBUS Process Bus Network
PROFIBUS is a digital process bus network capable of communicating
information between a master controller and an intelligent, slave process field
device, as well as from one host to another. It is based on a token bus/floating
master system. There are three different types of PROFIBUS: PROFIBUS-FMS, -DP and –PA:
The PROFIBUS-FMS network is the universal solution for
communicating between the field device level and the
supervisory systems.
The PROFIBUS-DP network is used when fast communications
are needed. The PROFIBUS-DP is a suitable replacement for
24-Volt parallel and 4–20 mA wiring interfaces.
The PROFIBUS-PA network is the process automation version
of the PROFIBUS network. It provides bus-powered stations
and intrinsic safety.
IV- 5- 2-2- I/O BUS NETWORK ADDRESSING:
Addressing of the I/O devices in an I/O bus networkoccurs during the configuration,
or programming, of the devices in the system. Depending on the PLC, this addressing can be
done either directly on the bus network via a PC orthrough a PC connected directly to the bus
network interface. It can also be done through the PLC’s RS-232 port.
IV -6- NETWORK PROTOCOLS
A protocol is a set of rules that two or more devices must follow if they are to
communicate with each other. Protocol includes everything from the meaning of data to the
voltage levels on connection wires. A network protocol defines how a network will handle the
following problems and tasks:
• Communication line errors
• flow control (to keep buffers from overflowing)
• Access by multiple devices
• Failure detection
• Data translation
• Interpretation of messages
IV -6-1- OSI REFERENCE MODEL
Networks follow a protocol to implement the transmission and reception of data over
the network medium. In 1979, the International Standards Organization (ISO) published the
Open Systems Interconnection (OSI) reference model to provide guidelines for network
protocols. This model divides the functions that protocols must perform into seven
hierarchical layers (see Figure II-9). Each layer interfaces only with its adjacent layers and is
unaware of the existence of the other layers. Figure II-9 describes the seven layers of the OSI.
The OSI model further subdivides the second layer into two sub-layers, 2A and 2B, called
protocols, the physical layer (layer 1) and the medium access control sub-layer (layer 2A) are
usually implemented with hardware, while the remaining layers are implemented using
software. The hardware components of layers 1 and 2A are generally referred to as modems
(or transceivers) and drivers (or controllers), respectively.
IV -6-2- IEEE STANDARDS
The Institute of Electrical and Electronic Engineers (IEEE) computer society
established the Standards Project 802 in 1980 for the purpose of developing a local area
network standard that would allow equipment from different manufacturers to communicate
through a local area network. After studying all the users’ and manufacturers’ requirements,
the committee developed standards that define several types of local networks. The open
system interconnection, OSI or seven layers model, is undoubtedly becoming the standard
model for communications definition.
Whereas RS232 and IEEE 802.3 for instance are interface standards, the OSI model is
an attempt to set up standards for the whole communications structure. In this model, the
different parts of the IEEE 802 standard and its relationship to the OSI model.
IV -6-3- TCP/IP PROTOCOL:
Most manufacturers who offer Ethernet compatibilityto implement supervisory
functions over equipment controlling plant floor functions use a TCP/IP protocol for layers 3
and 4 of the OSI model. The transmission control protocol/internet protocol (TCP/IP) was
initially developed for Arpanet, a computer networkcreated in the early 1970s in the United
States. The U.S. Department of Defense established this protocol to communicate information
in a reliable manner from one computer to another over the Arpanet network.
Nowadays, the TCP/IP protocol is used in the Internet data network. In the TCP/IP
protocol, the TCP guarantees control of end-to-end connections. The TCP makes several
services available to the user, such as the establishment of network connections and
disconnections, guaranteed data sequencing, protection against loss of sequence, connection
time control, and transparent multiplexing and transport of data. The IP (internet protocol)
performs complementary functions such as addressingnetwork data, distributing data
packages, and routing data in multi-network systems. Some PLC manufacturers offer
programmable controllers with TCP/IP over-Ethernet protocol built into the PLC processor
(see Figure II-11). This allows the PLC to connect directly to a supervisory Ethernet network.
Note that the PLC in Figure II-11 can also have a control network with other PLCs. These
TCP/IP model and the encapsulation process of data to be sent over the network bus.
IV-6-4- FIELD-BUS NETWORK PROTOCOLS:
The FIELDBUS network protocol is based on three layers of the ISO’s model. These
three layers are layer 1 (physical interface), layer 2 (data link), and layer 7 (application). In
addition to the ISO’s model, FIELDBUS adds an extralayer on top of the application layer
called the user layer. This user layer provides several key functions, which are function
blocks, device description services, and system management.
IV-6-5- PROFI-BUS NETWORK PROTOCOLS:
A-Profibus Network Protocol:
The PROFIBUS network follows the ISO model; however, each type of
PROFIBUS network contains slight variations in the model’s layers.
B-4The physical layer:
The physical layer specifies the type of PROFIBUS transmission medium. The
RS-485 voltage standard is defined for the FMS and DP versions of PROFIBUS. The
IEC 1158-2 standard is used in the PA version. For FMS and DP a maximum number
of 255 stations are possible.
• FMS (RS-485): 187.5 kbps General use.
• DP (RS-485): 500 kbps /1.5 Mbps/12 Mbps Fast devices.
• PA (IEC 1158-2): 31.25 kbps intrinsically safe.
C-Data link layer
The data link layer is defined by PROFIBUS as the FIELDBUS data link Layer
(FDL). The medium access control (MAC) part of the FDL defines when a station
may transmit data. The MAC ensures that only one station transmits data at any given
time. PROFIBUS communication is termed hybrid medium access. Through this
hybrid medium access protocol, a PROFIBUS network can function as a master-slave
system, a master-master system (token passing), or a combination of both systems.
D-The application layer:
This consists of two sections:
• FIELDBUS message specification (FMS) which provides powerful
network communication services and user interfaces
• Lower layer interface (LLI) conducts the data flow control and connection
monitoring.
V - DCS software components:
Many DCS systems employ commercial proprietary software upon which the DCS
system is developed. The proprietary software is often configured for a specific hardware
platform and may not interface with the software orhardware produced by competing
vendors. A wide range of commercial off-the-shelf (COTS) software products also are
available, some of which may suit the required application. COTS software usually is more
flexible, and will interface with different types of hardware and software. Software products
typically used within a DCS system are as follows:
• Computers operating system: Software used to control the central host computer
hardware. The software can be based on UNIX, Windows or other operating systems.
• Operator terminal operating system: Software usedto control the central host
computer hardware. The software is usually the sameas the central host computer
operating system. This software, along with that for the central host computer,
usually contributes to the networking of the central host and the operator terminals.
• Computer application: Software that handles the transmittal and reception of data to
and from the RTUs and the central host. The software also provides the graphical
user interface which offers site mimic screens, alarm pages,, and control functions.
• Operator terminal application: Application that enables users to access information
available on the central host computer application.It is usually a subset of the
software used on the central host computers.
• Communications protocol drivers: Software that isusually based within the central
host and the RTUs, and is required to control the translation and interpretation of the
data between ends of the communications links in the system. The protocol drivers
prepare the data for use either at the field devices or the central host end of the
system.
• Communications network management software: Software required to control the
communications network and to allow them to be monitored for performance and
failures.
• RTU automation software: Software that allows engineering staff to configure and
maintain the application housed within the RTUs (orPLCs). Most often this includes
the local automation application and any data processing tasks that are performed
within the RTU.
Commentaires
Enregistrer un commentaire